MMTCPDIOAIO - DIGITAL + ANALOG INPUTS/OUTPUTS

The MMTCPDIOAIO module is a multipurpose combination of inputs and outputs. The module can accommodate either 2 or 3 wire RTD sensors, current (0-20mA) and voltage (0-10V) inputs, current (0-20mA) or voltage (0-10V) output, and digital inputs and outputs. 

RTD INPUTS:

There are 2 RTD inputs on the module. The RTD resistance is read by the module circuitry, linearised and converted to degrees Centigrade. No ranging is required as the module covers the full range of the RTD as indicated in the RTD table.  The value that is read from the Modbus register is the actual temperature in degrees centigrade to 0.1°C resolution. ie: a value of 3451 corresponds to a temperature of 345.1°C. 

The RTD type is setup by writing a value to the RTD Type register. The value is obtained from the table below. For example to select a PT100 RTD, the value "1" must be written to the RTD Type register. 

A value of -32767 is used to indicate downscale burnout. 

Note: As there is no inter-channel isolation, isolated RTD's must be used in order to prevent ground loops and reading errors. 

ANALOG INPUTS:

The Analog Inputs (2) can be configured by internal jumpers as either a current input (0-20mA) or a voltage input (0-10V).  

An input of 0 - 20mA input current or 0 – 10V input voltage represents an output value of 0 - 4095 (12 bits) in the corresponding Modbus register. 

ANALOG OUTPUT:

There is a single analog output which can be configured with internal jumpers for a current output (0-20mA) or voltage output (0-10V). 

The resolution is 12 bits, so writing a value to the Modbus register for each output  of 0 - 4095 would give an output current of 0 - 20mA. A value of 819 ± 1LSB will give a current output of 4mA. 

DIGITAL INPUTS:

There are 5 digital inputs on the module. The inputs have internal pull-up resistors and are switched to negative. 

The first 2 inputs have got counters associated with them. The counters operate in three modes. 

In mode 0 all the counters are disabled. 

In mode 1 all counters are 32 bit counters allowing a count value from 0 to 4294967295. The count value can be cleared by writing a zero to the associated registers or preset to any other value using the same method. 

In mode 2 the inputs are connected as up/down counters. Input 1 will increment counter 1 whilst input 2 decrements counter1. 

Note: The count values are not battery backed-up and will be lost if power is turned off. 

The format of the registers allows the status of the inputs to be read as either single bits or all at once as a single register on the Modbus network. 

DIGITAL OUTPUTS:

The module has 2 open collector (NPN) digital outputs. The outputs may be used to drive lamps or external relays when more drive capability is required. 

The outputs are written to by the Modbus master device such as a PC or PLC. Each output can be individually switched on or off, or all outputs can be set up at the same time by writing a single number to the output register which represents the status of all outputs. 

An output watchdog timer can be configured to switch off all the outputs if there has been no communications with the module for up to 255 seconds. A value of 0 seconds will disable this timer and the outputs will remain in the last programmed state.

Each MMTCPDIOAIO Module has a unique Ethernet IP address which must be programmed into the PC or PLC. The IP address in the MMTCPDIOAIO Module is configured via the Web Server. Any standard Web browser such as Internet Explorer can be used to access the web pages were configuration is carried out. The converters are factory programmed with a default IP address of 169.254.111.111. This address must be changed before the converter is added to an existing network. 

The web page address for viewing the input/output status parameters is http://169.254.111.111/index.htm  and the address for viewing the configuration is http://169.254.111.111/tconfig.htm.

The web page address for configuring the module is http://169.254.111.111/ip.htm .

SPECIFICATIONS

Power Supply: (Logic)              10 - 26 Vdc @   140 mA
                           (Field)               10 - 26 Vdc @   40 mA 

Inputs: 2 or 3 Wire

            RTD             Type             Range             Accuracy             Standard

            1         -     PT100         -200 to 850 °C         0.3°C             IEC 751:1983
            2         -     Ni120           -80 to 320 °C         0.3°C

Resolution 0.1°C
Drift 100ppm/°C Typ.
Line resistance effect < 0.1°C balanced
Max. line resistance 100ohms

Analog Inputs: 
          
Voltage                          0(2) - 10 Vdc
          
Current                          0(4) - 20 mA
          
Input Resistance (Volts)   190kohms
          
Input Resistance (Current)   250ohms
          
Resolution                     12 bits
          
Drift                             100ppm/°C
          
Accuracy                       0.2% of span

Analog Outputs:
          
Current                         0(4) - 20 mA
          
Resolution                     12 bits
          
Drift                             100ppm/°C typ.
          
Accuracy                        0.05% of span
          
Compliance                   1000 ohms max. @ 24Vdc   500 ohms max. @ 12Vdc 

           Voltage                         0(2) - 10 V
          
Resolution                      12 bits
          
Drift                              100ppm/°C typ.
          
Accuracy                        0.05% of span
          
Compliance                    2000 ohms min. load 

Digital Inputs:
          
Supply Voltage                10 - 26 Vdc (Internal) switch to negative
          
Input Current                   2 mA @ 12Vdc / 4 mA @ 24Vdc

Counters:
           
Inputs                           1 & 2
           
Resolution                     32 Bits
           
Frequency                     50 Hz (Max)
            Pulse Width                  20 ms (min) 

Digital Outputs: 
           Open Collector NPN
            Maximum Voltage           36 Vdc
            Maximum Current           100 mA
           
Vceon                            1.1V  Max.

Ethernet:        10BaseT - 10Mbits/s twisted pair

Connector:       11 Pin Connector on rear of unit
                       RJ45 on front of module for 10Base-T Ethernet
                      
18 Way screw connector on front                                                 

Note: Inputs 1 & 2 are used as both digital inputs and counter inputs.  

WIRING

   

CONFIGURATION

The Web page address "169.254.111.111/ip.htm" is entered into the address line of the browser window to access the configuration page. This page allows you to change the IP address of the MOD-MUX TCP Module and to enter a Module Description Name and Input Names for identification/maintenance purposes.

 

IP Address: The new IP address can be entered into the web page as shown above. After this has been done, you must click the Submit button to send the values to the MOD-MUX TCP Module. The screen will now be updated and if successful will continue to display the new IP address. The new IP address will only be effective after the MOD-MUX TCP Module power has been switched off and on again. This feature allows you to check that the correct IP address has been entered before being activated. If the IP address has been entered incorrectly and the power has not been switched off, it is possible to re-enter the correct IP address. If the power has been switched off and back on again, the MOD-MUX TCP Module will not communicate until you enter the new IP address into the address line of the browser window.
Module Name: This field allows you to enter a module description name into the MOD-MUX TCP Module. This is an identifier for diagnostic/maintenance purposes and is chosen to best describe the MOD-MUX TCP Module in the system by name or number.
Input/Output Names: These fields allow you to enter an input description name into the MOD-MUX TCP Module. This is an identifier for diagnostic/maintenance purposes and is chosen to best describe the particular input/output by name or number. 
VIEWING WEB PAGES

To view the default Web page in the MOD-MUX TCP Module, start the Web browser and type "169.254.111.111" into the address line of the browser window. The main page will now be displayed in the browser window. 

 

Input Number: This refers to the actual input number on the terminals of the module.
Input Name: This is the name that was entered in the configuration page to best describe the inputs.
State: This is the current state of the inputs. To get an updated reading it is necessary to refresh the browser window to upload the web page again.

To view the Configuration Web page in the MOD-MUX TCP Module, start the Web browser and type "169.254.111.111/tconfig.htm" into the address line of the browser window.  

 

 

RTD Type: This is the type of RTD the module has been configured to operate with.
Input / Output Type: This is the type of analog input or output: 1 = 0-20mA and 2 = 0-10V.
Counter Mode: This determines the mode of the counter. Refer to the description above.
Output Watchdog: This is the time that the outputs will keep their active state after communications has stopped. If the value is zero(0) then the outputs will not time out and the last state will remain as long as power is applied to the module.

 