MMTCPDIOAIO - DIGITAL + ANALOG INPUTS/OUTPUTS
The
MMTCPDIOAIO module is a multipurpose combination of inputs and outputs. The
module can accommodate either 2 or 3 wire RTD sensors, current (0-20mA) and
voltage (0-10V) inputs, current (0-20mA) or voltage (0-10V) output, and digital
inputs and outputs. RTD
INPUTS: There are 2
RTD inputs on the module. The RTD resistance is read by the module circuitry,
linearised and converted to degrees Centigrade. No ranging is required as the
module covers the full range of the RTD as indicated in the RTD table.
The value that is read from the Modbus register is the actual temperature
in degrees centigrade to 0.1°C resolution. ie: a value of 3451 corresponds to a
temperature of 345.1°C. The RTD type
is setup by writing a value to the RTD Type register. The value is obtained from
the table below. For example to select a PT100 RTD, the value "1" must
be written to the RTD Type register. A value of
-32767 is used to indicate downscale burnout. Note: As there
is no inter-channel isolation, isolated RTD's must be used in order to prevent
ground loops and reading errors. ANALOG
INPUTS: The Analog
Inputs (2) can be configured by internal jumpers as either a current input
(0-20mA) or a voltage input (0-10V). An input of 0
- 20mA input current or 0 – 10V input voltage represents an output value of 0
- 4095 (12 bits) in the corresponding Modbus register. ANALOG
OUTPUT: There is a
single analog output which can be configured with internal jumpers for a current
output (0-20mA) or voltage output (0-10V). The resolution
is 12 bits, so writing a value to the Modbus register for each output
of 0 - 4095 would give an output current of 0 - 20mA. A value of 819 ±
1LSB will give a current output of 4mA. DIGITAL
INPUTS: There are 5
digital inputs on the module. The inputs have internal pull-up resistors and are
switched to negative. The first 2
inputs have got counters associated with them. The counters operate in three
modes. In mode
0 all the counters are disabled. In mode
1 all counters are 32 bit counters allowing a count value from 0 to
4294967295. The count value can be cleared by writing a zero to the associated
registers or preset to any other value using the same method. In mode
2 the inputs are connected as up/down counters. Input 1 will increment
counter 1 whilst input 2 decrements counter1. Note: The count values are not battery backed-up and will be lost if power is
turned off. The format of
the registers allows the status of the inputs to be read as either single bits
or all at once as a single register on the Modbus network. DIGITAL
OUTPUTS: The module has
2 open collector (NPN) digital outputs. The outputs may be used to drive lamps
or external relays when more drive capability is required. The outputs
are written to by the Modbus master device such as a PC or PLC. Each output can
be individually switched on or off, or all outputs can be set up at the same
time by writing a single number to the output register which represents the
status of all outputs. An output watchdog timer can be configured to switch off all the outputs if there has been no communications with the module for up to 255 seconds. A value of 0 seconds will disable this timer and the outputs will remain in the last programmed state. Each
MMTCPDIOAIO Module has a unique Ethernet IP address which must be programmed
into the PC or PLC. The IP address in the MMTCPDIOAIO Module is configured via
the Web Server. Any standard Web browser such as Internet Explorer can be used
to access the web pages were configuration is carried out. The converters are
factory programmed with a default IP address of 169.254.111.111. This address
must be changed before the converter is added to an existing network. The web page
address for viewing the input/output status parameters is http://169.254.111.111/index.htm
and the address for viewing the configuration is http://169.254.111.111/tconfig.htm.
The web page address for configuring the module is http://169.254.111.111/ip.htm .
Power Supply: (Logic)
10 - 26 Vdc @ 140 mA Inputs: 2 or 3 Wire RTD Type Range Accuracy Standard
1 -
PT100 -200 to 850
°C
0.3°C
IEC 751:1983
Analog Inputs: Analog Outputs:
Voltage
0(2) - 10 V Digital Inputs: Counters: Digital Outputs: Ethernet: 10BaseT - 10Mbits/s twisted pair Connector:
11 Pin Connector on rear of unit Note: Inputs 1 & 2 are used as both digital inputs and counter inputs.
The Web page
address "169.254.111.111/ip.htm" is entered into the address
line of the browser window to access the configuration page. This page allows
you to change the IP address of the MOD-MUX TCP Module and to enter a Module
Description Name and Input Names for identification/maintenance purposes.
To view the
default Web page in the MOD-MUX TCP Module, start the Web browser and type
"169.254.111.111" into the address line of the browser window. The
main page will now be displayed in the browser window.
To view the
Configuration Web page in the MOD-MUX TCP Module, start the Web browser and type
"169.254.111.111/tconfig.htm" into the address line of the
browser window.
|
|