MMTCP8TC
- THERMOCOUPLE INPUTS
The
thermocouple voltage is read by the module circuitry, linearised and converted
to degrees Centigrade. No ranging is required as the module covers the full
temperature range of the thermocouple. The value that is read from the Modbus
register is the actual temperature in degrees centigrade to 0.1°C resolution.
ie: a value of 3451 corresponds to a temperature of 345.1°C. The
thermocouple type is setup by writing a value to the TC Type register. The value
is obtained from the table below. For example to select type K thermocouples,
the value "2" must be written to the TC Type register. All 8
thermocouple inputs adopt the same TC type. A value of
-32767 is used to indicate downscale burnout. The module has
built in Cold Junction Compensation. Use must be made of the correct
thermocouple extension wire to avoid reading errors. The
thermocouple module can also be configured for a 0 - 50mV input range. The TC
Type register must be set to 9 for this option. The value in the register which
is read back over the network is 0 - 50,000. Note: As there
is no inter-channel isolation, isolated thermocouples must be used in order to
prevent ground loops and reading errors. Each MMTCP8TC
Module has a unique Ethernet IP address which must be programmed into the PC or
PLC. The IP address in the MMTCP8TC Module is configured via the Web Server. Any
standard Web browser such as Internet Explorer can be used to access the web
pages were configuration is carried out. The converters are factory programmed
with a default IP address of 169.254.111.111. This address must be changed
before the converter is added to an existing network. The web page
address for viewing the Thermocouple input parameters is http://169.254.111.111/index.htm
and the address for viewing the configuration data is http://169.254.111.111/tconfig.htm.
The web page
address for configuring the module is http://169.254.111.111/ip.htm
.
Power Supply: (Logic)
10 - 26 Vdc @ 140 mA
TC
Type
Range
Accuracy Resolution 0.1°C Drift 100ppm/°C Typ. Isolation 1000Vrms between field and logic CJC error: ±1.0°C Typ. Ethernet: 10BaseT - 10Mbits/s twisted pair Connector:
11 Pin Connector on rear of unit
The Web page
address "169.254.111.111/ip.htm" is entered into the address
line of the browser window to access the configuration page. This page allows
you to change the IP address of the MOD-MUX TCP Module, select the TC type, and
to enter a Module Description Name and Input Names for
identification/maintenance purposes.
To view the
default Web page in the MOD-MUX TCP Module, start the Web browser and type
"169.254.111.111" into the address line of the browser window. The
main page will now be displayed in the browser window.
To view the
Configuration Web page in the MOD-MUX TCP Module, start the Web browser and type
"169.254.111.111/tconfig.htm" into the address line of the
browser window.
|
|