MMTCP8AI/I ISO

         

MMTCP8AI/I ISO - ISOLATED CURRENT INPUTS   

The MMTCP8AI/I ISO module is a 8 channel isolated current input module. The module uses differential inputs to reduce effects of electrical noise and mains pickup. The current inputs are isolated from the logic and from each other. 

The current input can be represented in a number of formats according to the type which is setup by writing a value to the Type register. The value is obtained from the table below. 

The standard setting for the MMTCP8AI/I ISO module is 0 - 20mA input current which represents an output value of 0 - 4095 (12 bits) in the corresponding Modbus register.  4 mA would give a reading of 819 ± 1LSB.  

The module can also be configured for a 0 – 20.000mA input range or +/- 20.000mA input.  

Each MMTCP8AI/I ISO Module has a unique Ethernet IP address which must be programmed into the PC or PLC. The IP address in the MMTCP8AI/I ISO Module is configured via the Web Server. Any standard Web browser such as Internet Explorer can be used to access the web pages were configuration is carried out. The converters are factory programmed with a default IP address of 169.254.111.111. This address must be changed before the converter is added to an existing network. 

The web page address for viewing the input parameters is http://169.254.111.111/index.htm  and the address for viewing the configuration data is http://169.254.111.111/tconfig.htm.

The web page address for configuring the module is http://169.254.111.111/ip.htm .

SPECIFICATIONS

Power Supply: 10 - 26Vdc           90 mA @ 24VDC / 160mA @ 12VDC
Inputs:                Current

            Input Type                     Range                           Resolution 
            
                                 0 – 4095                        (12 bits)
            
      2                            0 – 20.000 mA                  1uA
            
      3                            +/-  20.000 mA                  1uA

               Isolation                            1000Vrms between field and logic
   
                                           350Vpeak between each current input
              
Drift                                   100ppm/°C

 Ethernet:        10BaseT - 10Mbits/s twisted pair

Connector:       11 Pin Connector on rear of unit
                       RJ45 on front of module for 10Base-T Ethernet
                      
18 Way screw connector on front  

WIRING

 

 

 

CONFIGURATION

The Web page address "169.254.111.111/ip.htm" is entered into the address line of the browser window to access the configuration page. This page allows you to change the IP address, default gateway and subnet mask of the MOD-MUX TCP Module,  select the Input type, and to enter a Module Description Name and Input Names for identification/maintenance purposes.

   

IP Address: The new IP address can be entered into the web page as shown above. After this has been done, you must click the Submit button to send the values to the MOD-MUX TCP Module. The screen will now be updated and if successful will continue to display the new IP address. The new IP address will only be effective after the MOD-MUX TCP Module power has been switched off and on again. This feature allows you to check that the correct IP address has been entered before being activated. If the IP address has been entered incorrectly and the power has not been switched off, it is possible to re-enter the correct IP address. If the power has been switched off and back on again, the MOD-MUX TCP Module will not communicate until you enter the new IP address into the address line of the browser window.
Default Gateway IP Address: If the MOD-MUX TCP Module is on a different network to your PC you may need to setup the IP address of the gateway.
Subnet Mask: The subnet mask must also be entered if the default gateway setting is used. A subnet mask of 000.000.000.000 will disable the default gateway setting.
Socket Timeout: The MOD-MUX TCP Module communicates using sockets which are part of the TCP/IP protocol. The module has 5 sockets. If a communication link is lost with the Modbus master, then there exists the possibility that the socket stays open and is no longer accessible. The timeout facility is reset each time a valid Modbus message is received and the socket stays open. If there is no activity then the socket will timeout and send a message to the Modbus master indicating that the socket is closing.
Input Type: The type for the module can be configured by entering the corresponding number from the list in the specifications.

  

Module Name: This field allows you to enter a module description name into the MOD-MUX TCP Module. This is an identifier for diagnostic/maintenance purposes and is chosen to best describe the MOD-MUX TCP Module in the system by name or number.
Input Names: These fields allow you to enter an input description name into the MOD-MUX TCP Module. This is an identifier for diagnostic/maintenance purposes and is chosen to best describe the particular input by name or number.

  

VIEWING WEB PAGES

 To view the default Web page in the MOD-MUX TCP Module, start the Web browser and type "169.254.111.111" into the address line of the browser window. The main page will now be displayed in the browser window.

 

 

Channel Number: This refers to the actual input number on the terminals of the module.
Channel Name: This is the name that was entered in the configuration page to best describe the inputs.
Value: This is the current value of the inputs. To get an updated reading it is necessary to refresh the browser window to upload the web page again.

To view the Configuration Web page in the MOD-MUX TCP Module, start the Web browser and type "169.254.111.111/tconfig.htm" into the address line of the browser window.

  

Input Type: This is the format that the module has been configured to operate with.
Line Frequency: Depending on the mains frequency this can be either 50 or 60 Hz

 

 