MMTCP6RTD

         

MMTCP6RTD - RTD INPUTS

 

The MMTCP6RTD module is a 6 RTD input module. The module can accommodate either 2 or 3 wire RTD sensors. The RTD inputs are isolated from the logic. 

The RTD resistance is read by the module circuitry, linearised and converted to degrees Centigrade. No ranging is required as the module covers the full range of the RTD. The value that is read from the Modbus register is the actual temperature in degrees centigrade to 0.1°C resolution. ie: a value of 3451 corresponds to a temperature of 345.1°C. 

The RTD type is setup by writing a value to the RTD Type register . The value is obtained from the table below. For example to select a PT100 RTD, the value "1" must be written to the RTD Type register. All 6 RTD inputs adopt the same RTD type. 

A value of  -32767 is used to indicate downscale burnout.

Note: As there is no inter-channel isolation, isolated RTD's must be used in order to prevent ground loops and reading errors. 

Each MMTCP6RTD Module has a unique Ethernet IP address which must be programmed into the PC or PLC. The IP address in the MMTCP6RTD Module is configured via the Web Server. Any standard Web browser such as Internet Explorer can be used to access the web pages were configuration is carried out. The converters are factory programmed with a default IP address of 169.254.111.111. This address must be changed before the converter is added to an existing network. 

The web page address for viewing the RTD input parameters is http://169.254.111.111/index.htm  and the address for viewing the configuration is http://169.254.111.111/tconfig.htm.

The web page address for configuring the module is http://169.254.111.111/ip.htm .

 

SPECIFICATIONS

Power Supply: (Logic)    10 - 26 Vdc @    140 mA

Inputs: 2 or 3 Wire

            RTD             Type             Range             Accuracy             Standard
            1         -     PT100         -200 to 850 °C         0.3°C             IEC 751:1983
            2         -     Ni120           -80 to 320 °C         0.3°C

Resolution         0.1°C

Drift                 100ppm/°C Typ.

Line resistance effect < 0.1°C balanced

Max. line resistance 100ohms

Isolation 1000Vrms between field and logic

Ethernet:        10BaseT - 10Mbits/s twisted pair

Connector:       11 Pin Connector on rear of unit
                       RJ45 on front of module for 10Base-T Ethernet
                      
18 Way screw connector on front  

WIRING

 

 

 

 

 

 

CONFIGURATION

The Web page address "169.254.111.111/ip.htm" is entered into the address line of the browser window to access the configuration page. This page allows you to change the IP address of the MOD-MUX TCP Module, select the RTD type, and to enter a Module Description Name and Input Names for identification/maintenance purposes. 

IP Address: The new IP address can be entered into the web page as shown above. After this has been done, you must click the Submit button to send the values to the MOD-MUX TCP Module. The screen will now be updated and if successful will continue to display the new IP address. The new IP address will only be effective after the MOD-MUX TCP Module power has been switched off and on again. This feature allows you to check that the correct IP address has been entered before being activated. If the IP address has been entered incorrectly and the power has not been switched off, it is possible to re-enter the correct IP address. If the power has been switched off and back on again, the MOD-MUX TCP Module will not communicate until you enter the new IP address into the address line of the browser window.
RTD Type: The RTD type for the module can be configured by entering the corresponding number from the list in the specifications.
Module Name: This field allows you to enter a module description name into the MOD-MUX TCP Module. This is an identifier for diagnostic/maintenance purposes and is chosen to best describe the MOD-MUX TCP Module in the system by name or number.
Input Names: These fields allow you to enter an input description name into the MOD-MUX TCP Module. This is an identifier for diagnostic/maintenance purposes and is chosen to best describe the particular input by name or number. 
VIEWING WEB PAGES

To view the default Web page in the MOD-MUX TCP Module, start the Web browser and type "169.254.111.111" into the address line of the browser window. The main page will now be displayed in the browser window. 

 

Channel Number: This refers to the actual input number on the terminals of the module.
Channel Name: This is the name that was entered in the configuration page to best describe the inputs.
Value: This is the current temperature of the inputs. To get an updated reading it is necessary to refresh the browser window to upload the web page again.

To view the Configuration Web page in the MOD-MUX TCP Module, start the Web browser and type "169.254.111.111/tconfig.htm" into the address line of the browser window.  

 

 

Input Type: This is the type of RTD the module has been configured to operate with.
Line Frequency: Depending on the mains frequency this can be either 50 or 60 Hz.

 

 