MMTCP16DO - DIGITAL OUTPUTS
The outputs
are written to by the Modbus master device such as a PC or PLC. Each output can
be individually switched on or off, or all outputs can be set up at the same
time by writing a single number to the output register which represents the
status of all outputs. An output
watchdog timer can be configured to switch off all the outputs if there has been
no communications with the module for up to 255 seconds. A value of 0 seconds
will disable this timer and the outputs will remain in the last programmed
state. Each MMTCP16DO
Module has a unique Ethernet IP address which must be programmed into the PC or
PLC. The IP address in the MMTCP16DO Module is configured via the Web Server.
Any standard Web browser such as Internet Explorer can be used to access the web
pages were configuration is carried out. The converters are factory programmed
with a default IP address of 169.254.111.111. This address must be changed
before the converter is added to an existing network. The web page
address for viewing the digital output status parameters is http://169.254.111.111/index.htm
The web page
address for configuring the module is http://169.254.111.111/ip.htm
Power Supply: (Logic)
10 - 26 Vdc @ 140 mA Outputs:
Open Collector NPN Ethernet: 10BaseT - 10Mbits/s twisted pair Connector:
11 Pin Connector on rear of unit
The Web page
address "169.254.111.111/ip.htm" is entered into the address
line of the browser window to access the configuration page. This page allows
you to change the IP address of the MOD-MUX TCP Module and to enter a Module
Description Name and Output Names for identification/maintenance purposes.
To view the
default Web page in the MOD-MUX TCP Module, start the Web browser and type
"169.254.111.111" into the address line of the browser window. The
main page will now be displayed in the browser window.
|
|