MMTCP16DI - DIGITAL INPUTS WITH COUNTERS
The
counters operate in three modes. In mode
0 all the counters are disabled. In mode
1 the first eight inputs (1-8) have internal counters associated with them.
These counters are 32 bit counters allowing a count value from 0 to 4294967295.
The count value can be cleared by writing a zero to the associated registers or
preset to any other value using the same method. In mode
2 the inputs are connected as up/down counters. Input 1 will increment
counter 1 whilst input 2 decrements counter1. In the same way, inputs 3&4
operate counter 2, inputs 5&6 operate counter 3 and inputs 7&8 operate
counter 4. Note: The count values are not battery backed-up and will be lost if power is
turned off. The format of
the registers allows the status of the inputs to be read as either single bits
or all at once as a single register on the Modbus network. Each MMTCP16DI
Module has a unique Ethernet IP address which must be programmed into the PC or
PLC. The IP address in the MMTCP16DI Module is configured via the Web Server.
Any standard Web browser such as Internet Explorer can be used to access the web
pages were configuration is carried out. The converters are factory programmed
with a default IP address of 169.254.111.111. This address must be changed
before the converter is added to an existing network. The web page
address for viewing the digital input status parameters is http://169.254.111.111/index.htm
and the address for viewing the counters is http://169.254.111.111/counters.htm.
The web page
address for configuring the module is http://169.254.111.111/ip.htm
and the web page for configuring the counters is http://169.254.111.111/countcfg.htm
.
Power Supply: 10 - 26 Vdc @ 140 mA Inputs:
Supply Voltage 10 - 26 Vdc Counters:
Inputs 1 to 8 Ethernet: 10BaseT - 10Mbits/s twisted pair Connector:
11 Pin Connector on rear of unit
Note: Inputs 1 to 8 are used as both digital inputs and counter inputs.
The Web page
address "169.254.111.111/ip.htm" is entered into the address
line of the browser window to access the configuration page. This page allows
you to change the IP address of the MOD-MUX TCP Module and to enter a Module
Description Name and Input Names for identification/maintenance purposes.
The Web page
address "169.254.111.111/countcfg.htm" is entered into the
address line of the browser window to access the counter configuration page.
This page allows you to enter a Counter Description Name for
identification/maintenance purposes.
To view the
default Web page in the MOD-MUX TCP Module, start the Web browser and type
"169.254.111.111" into the address line of the browser window. The
main page will now be displayed in the browser window.
To view the
Counter Web page in the MOD-MUX TCP Module, start the Web browser and type
"169.254.111.111/counter.htm" into the address line of the
browser window.
|
|
Send mail to proconel@proconel.com with
questions or comments about this web site.
|