Home Up

MMI/OMAP

I/O MAPPER

 

The I/O Mapper is used for point-to-point communications where it is required to send input information from a MM8DI or MM8AI input module to a MM8DO or MM8AO output module over the network. The I/O Mapper is the Modbus master and all I/O modules must be set up as slaves. The I/O Mapper is only required if there is more than one pair of modules on the network.

When the I/O Mapper is used, The ID's of the Digital modules must be set up in the range 0 to 31 and the Analog modules must be set up in the range 32 to 47, starting at the bottom of the range. The Input and Output modules must be set to the same ID.

SPECIFICATIONS

Power Supply: 10 - 26 Vdc @ 35 mA

Connector: 11 Pin Connector on rear of unit

         

WIRING

 

SWITCH SETTINGS

 

SWITCH

FUNCTION

DESCRIPTION

     

1

No. of Digital Modules

The number of digital input/output pairs to be mapped are set up with switches 1 to 5

2

No. of Digital Modules

 inclusive. Node ID’s for digital modules are from 0 to 31.

3

No. of Digital Modules

4

No. of Digital Modules

 

5

No. of Digital Modules

 

6

No. of Analog Modules

The number of Analog input/output pairs to be mapped

7

No. of Analog Modules

are set up with switches 6 to 9 inclusive. Node ID’s for

8

No. of Analog Modules

Analog modules are from 32 to 47.

9

No. of Analog Modules

 

10

BAUD RATE

Selects 9600 (off) or 19200 BAUD (on)

 
DIAGNOSTIC UNIT MENU FORMAT

                                                           

 

 

Send mail to proconel@proconel.com with questions or comments about this web site.