Home Up

MM8DIO

MM8DIO - DIGITAL INPUTS / OUTPUTS

The MM8DIO module is an 8 channel digital input and 8 channel digital output module. 

The inputs are isolated from the logic by bi-directional opto-couplers. The common is connected internally to either the -volts or +volts field power supply terminals using a jumper link which is situated inside the housing. 

The inputs have internal counters associated with them. These counters are 32 bit counters allowing a count value from 0 to 4294967295. The count value can be cleared by writing a zero to the associated registers or preset to any other value using the same method. The counters can also be reset automatically when read. This is done by setting on DIP switch 9 on the front panel. 

Note: The count values are not battery backed-up and will be lost if power is turned off. 

The format of the registers allows the status of the inputs to be read as either single bits or all at once as a single register on the Modbus network. 

The 8 digital outputs are open collector (NPN). The outputs may be used to drive lamps or external relays when more drive capability is required. The outputs are isolated from the logic and they share a common negative terminal. 

When used as a slave module, the outputs are written to by the Modbus master device such as a PC or PLC. Each output can be individually switched on or off, or all outputs can be set up at the same time by writing a single number to the output register which represents the status of all outputs.

SPECIFICATIONS

Power Supply:   (Logic) 10 - 26 Vdc @ 50 mA
                        (Field) 20 - 26 Vdc @ 50 mA

Inputs:              Supply Voltage 10 - 26 Vdc
                       Supply Current 8 X 4 mA @ 12Vdc / 8 X 8 mA @ 24Vdc
                       Isolation 1500Vrms between field and logic

Counters:        Resolution 32 Bits
                     Frequency 500 Hz (Max)
                     Pulse Width 1ms (min)

Outputs:         Open Collector NPN
                     Maximum Voltage 36 Vdc
                     Maximum Current 100 mA
                     Isolation 1500Vrms between field and logic
                     Vceon 1.1V Max.

Connector: 11 Pin Connector on rear of unit
                 10 Way screw connector on front

Note: Inputs 1 to 8 are used as both digital inputs and counter inputs.

WIRING

SWITCH SETTINGS

SWITCH

FUNCTION

DESCRIPTION

     

1

NODE ID

Node ID’s from 0 to 127 are set up using switches 1 to 7.

2

NODE ID

3

NODE ID

 

4

NODE ID

 

5

NODE ID

 

6

NODE ID

 

7

NODE ID

 

8

INVERT

When switched ON the status of the inputs is inverted in the Modbus status register (30002).

9

CNTR

When switched ON the counters are automatically reset to zero when read.

10

BAUD RATE

Selects 9600 (off) or 19200 BAUD (on)

 

DIAGNOSTIC UNIT MENU FORMAT

                                                       

 

 

Send mail to proconel@proconel.com with questions or comments about this web site.