MM8AO - ANALOG OUTPUTS

The MM8AO is a 8 channel current output module. Each channel can be set to output a current in the range 0 - 20mA. The outputs are isolated from the logic and share a common negative terminal.

The resolution is 12 bits, so writing a value to the Modbus register for each output of 0 - 4095 would give an output current of 0 - 20mA. A value of 819 ± 1LSB will give a current output of 4mA.

The module may be used as either a slave or master on the Modbus network. When used with a PC or PLC the module will be configured as a slave. When used with a MM8AI module in a point-to-point configuration, the DIP switch 9 must be turned on to set the module up as a master. In this mode the MM8AO module will automatically read the information from the MM8AI module and write the input status to the outputs.

When used as a slave module, the outputs are written to by the Modbus master device such as a PC or PLC.

 

SPECIFICATIONS

Power Supply: Logic 10 - 26 Vdc @ 50 mA

                     Field 10 - 26 Vdc @ 185 mA

Outputs:

Current 0(4) - 20 mA

Resolution 12 bits

Isolation 1500Vrms between field and logic

Drift 100ppm/°C typ.

Accuracy 0.05% of span

Compliance 1000 ohms max. @ 24Vdc 500 ohms max. @ 12Vdc

Connector: 11 Pin Connector on rear of unit

                 10 Way screw connector on front

         

WIRING

SWITCH SETTINGS

 

SWITCH

FUNCTION

DESCRIPTION

     

1

NODE ID

Node ID’s from 0 to 127 are set up using switches 1 to 7.

2

NODE ID

3

NODE ID

 

4

NODE ID

 

5

NODE ID

 

6

NODE ID

 

7

NODE ID

 

8

-

Not used.

9

MODE

Selects Master or Slave Mode. Master mode is used when the module is connected to a single Analog input module. Slave mode is used when the module is to be polled either by the I/O Mapper or by a PC.

10

BAUD RATE

Selects 9600 (off) or 19200 BAUD (on)

 