Home Up

MM8AI

8 ANALOG INPUTS

The Analog Input modules are supplied as either a current input module (MM8AI/I) or a voltage input module (MM8AI/V). The inputs are isolated from the logic and share a common negative terminal.

The standard setting for the MM8AI/I module is 0 - 20mA input current which represents an output value of 0 - 4095 (12 bits) in the corresponding Modbus register. To obtain an output value of 0 to 4095 for an input signal of 4 to 20mA the offset switch is switched on.

The same applies to the MM8AI/V module. An input voltage of 0 - 10Volts represents an output of 0 - 4095 and 2 volts would give a reading of 819 ± 1LSB. To obtain an output value of 0 to 4095 for an input signal of 2 to 10V the offset switch is switched on. An input range of 0(1) to 5Vdc is available by removing the jumper link located on the analogue board inside the enclosure.

         

SPECIFICATIONS

Power Supply: Logic 10 - 26 Vdc @ 50 mA

                      Field 10 - 26 Vdc @ 25 mA

Inputs:

Voltage 0(2) - 10 Vdc or 0(1) - 5 Vdc - 8AI/V

Current 0(4) - 20 mA - 8AI/I

Input Resistance (8AI/V) 20kohms

Input Resistance (8AI/I) 250ohms

Resolution 12 bits

Isolation 1500Vrms between field and logic

Drift 100ppm/°C

Accuracy 0.2% of span

Connector: 11 Pin Connector on rear of unit

                 10 Way screw connector on front

         

WIRING

 

SWITCH SETTINGS

SWITCH

FUNCTION

DESCRIPTION

     

1

NODE ID

Node ID’s from 0 to 127 are set up using switches 1 to 7.

2

NODE ID

3

NODE ID

 

4

NODE ID

 

5

NODE ID

 

6

NODE ID

 

7

NODE ID

 

8

-

Not used.

9

OFFSET

When switched ON the inputs scaled to accept a 2V or 4mA offset .

10

BAUD RATE

Selects 9600 (off) or 19200 BAUD (on)

 
DIAGNOSTIC UNIT MENU FORMAT

                                                          

 

 