MM6RTD

6 RTD INPUTS

The MM6RTD module is a 6 RTD input module. The module can accommodate either 2 or 3 wire RTD sensors. The RTD inputs are isolated from the logic.

The RTD resistance is read by the module circuitry, linearised and converted to degrees Centigrade. No ranging is required as the module covers the full range of the RTD as indicated below. The value that is read from the Modbus register is the actual temperature in degrees centigrade to 0.1°C resolution. ie: a value of 3451 corresponds to a temperature of 345.1°C.

The RTD type is setup by writing a value to the RTD Type register . The value is obtained from the table below. For example to select a PT100 RTD, the value "1" must be written to the RTD Type register. All 6 RTD inputs adopt the same RTD type.

The DIP switch 9 is used to select upscale or downscale burnout for break detection. A value of 32768 is used to indicate upscale burnout and a value of -32767 is used to indicate downscale burnout.

 

Note: As there is no inter-channel isolation, isolated RTD's must be used in order to prevent ground loops and reading errors.

 

SPECIFICATIONS

Power Supply: Logic 10 - 26Vdc @ 80 mA

Inputs: 2 or 3 Wire

            RTD             Type             Range             Accuracy             Standard

            1         -     PT100         -200 to 850 °C         0.3°C             IEC 751:1983

            2         -     Ni120           -80 to 320 °C         0.3°C

Resolution 0.1°C

Drift 100ppm/°C Typ.

Line resistance effect < 0.1°C balanced

Max. line resistance 100ohms

Isolation 1000Vrms between field and logic

Connector: 11 Pin Connector on rear of unit

                 18 Way screw connector on front

WIRING

 

SWITCH SETTINGS

 

SWITCH

FUNCTION

DESCRIPTION

     

1

NODE ID

Node ID’s from 0 to 127 are set up using switches 1 to 7.

2

NODE ID

3

NODE ID

 

4

NODE ID

 

5

NODE ID

 

6

NODE ID

 

7

NODE ID

 

8

-

Not used.

9

BREAK

RTD break. When switched off the RTD value will loaded with -32767 when the RTD is faulty. When switched on the RTD value will be loaded with 32768.

10

BAUD RATE

Selects 9600 (off) or 19200 BAUD (on)

 
DIAGNOSTIC UNIT MENU FORMAT

                                                     

 

 