4 RELAY OUTPUTS
The MM4RO module has 4 normally open relay outputs. These modules may be used when a higher drive capability is required, or when isolation between outputs are required. The module may be used as either a slave or master on the Modbus network. When used with a PC or PLC the module will be configured as a slave. When used with a MM8DI module in a point-to-point configuration, the DIP switch 9 must be turned on to set the module up as a master. In this mode the MM4RO module will automatically read the information from the MM8DI module and write the input status of the first four inputs to the corresponding outputs. When used as a slave module, the outputs are written to by the Modbus master device such as a PC or PLC. Each output can be individually switched on or off, or all outputs can be set up at the same time by writing a single number to the output register which represents the status of all outputs.
Power Supply: (Logic) 10 - 26 Vdc @ 50 mA (Field) 20 - 26Vdc @ 105mA Outputs: Normally Open Relay Contacts Maximum Voltage 250VAC Maximum Current 0.5A @ 220VAC / 1A @ 28VDC Isolation 1000Vrms between field and logic 1000Vrms between outputs Connector: 11 Pin Connector on rear of unit 10 Way screw connector on front
|
|