MM16DO - DIGITAL OUTPUTS
This module has 16 open collector (NPN)
digital outputs. The outputs may be used to drive lamps or external relays when
more drive capability is required. The outputs are isolated from the logic and
they share a common negative terminal. The module may be used as either a slave
or master on the Modbus network. When used with a PC or PLC the module will be
configured as a slave. When used with a MM16DI module in a point-to-point
configuration, the DIP switch 9 must be turned on to set the module up as a
master. In this mode the MM16DO module will automatically read the information
from the MM16DI module and write the input status to the outputs. When used as a slave module, the outputs
are written to by the Modbus master device such as a PC or PLC. Each output can
be individually switched on or off, or all outputs can be set up at the same
time by writing a single number to the output register which represents the
status of all outputs. An
output watchdog timer can be configured to switch off all the outputs if there
has been no communications with the module for up to 255 seconds. A value of 0
seconds will disable this timer and the outputs will remain in the last
programmed state.
Power Supply: (Logic) 10 - 26 Vdc @ 50 mA Outputs: Open Collector NPN Connector: 11 Pin Connector on rear of unit
|
|