MM16DI

MM16DI - DIGITAL INPUTS WITH COUNTERS

The MM16DI module is a 16 channel digital input module. The inputs are isolated from the logic by bi-directional opto-couplers. The inputs are divided into 2 isolated groups of 8 inputs each. This allows for many configurations in which the input module may be used. One such configuration could be where one group is connected as common positive and the second group connected as common negative.

The counters operate in three modes.

In mode 0 all the counters are disabled.

In mode 1 the first eight inputs (1-8) have internal counters associated with them. These counters are 32 bit counters allowing a count value from 0 to 4294967295. The count value can be cleared by writing a zero to the associated registers or preset to any other value using the same method. The counters can also be reset automatically when read. This is done by setting on DIP switch 9 on the front panel.

In mode 2 the inputs are connected as up/down counters. Input 1 will increment counter 1 whilst input 2 decrements counter1. In the same way, inputs 3&4 operate counter 2, inputs 5&6 operate counter 3 and inputs 7&8 operate counter 4.

Note: The count values are not battery backed-up and will be lost if power is turned off.

The format of the registers allows the status of the inputs to be read as either single bits or all at once as a single register on the Modbus network.

SPECIFICATIONS

Power Supply: 10 -26 Vdc @ 50 mA

Inputs:

Supply Voltage 10 - 26 Vdc

Supply Current 16 X 4 mA @ 12Vdc / 16 X 8 mA @ 24Vdc

Isolation 1500Vrms between field and logic

Counters:

Inputs 1 to 8

Resolution 32 Bits

Frequency 500 Hz (Max)

Pulse Width 1ms (min)

Connector: 11 Pin Connector on rear of unit

                 18 Way screw connector on front

Note: Inputs 1 to 8 are used as both digital inputs and counter inputs.

         

WIRING

 
SWITCH SETTINGS

 

SWITCH

FUNCTION

DESCRIPTION

     

1

NODE ID

Node ID’s from 0 to 127 are set up using switches 1 to 7.

2

NODE ID

3

NODE ID

 

4

NODE ID

 

5

NODE ID

 

6

NODE ID

 

7

NODE ID

 

8

INVERT

When switched ON the status of the inputs is inverted in the Modbus status register (30002).

9

CNTR

When switched ON the counters are automatically reset to zero when read.

10

BAUD RATE

Selects 9600 (off) or 19200 BAUD (on)

 