PL4RO – 4 Relay Output Module


The PL4RO module has 4 normally open/ normally closed relay outputs. These modules may be used when a higher drive capability is required, or when isolation between outputs are required.

An output watchdog timer can be configured to switch off all the outputs if there has been no communications with the module for up to 255 seconds. A value of 0 seconds will disable this timer and the outputs will remain in the last programmed state.
 

PL4RO – 4 RELAY OUTPUTS
Digital Outputs 4
Type Relay - 1 x Form C
Max Load Current 0.5Aac  / 1Adc.
Max load Voltage 220Vac / 28Vdc
Isolation (Field & Logic) 1000VAC RMS
Watch dog output timer Disable or 1-255 sec  adjustable
Status Indication LED for each channel
Power supply (Logic) +24Vdc




















Download ProLogic Manual

  